Reyds.Heat pumps · Boilers · Steam

Kwikot Industrial Water Heater · KS100

Kwikot Industrial Water Heater Installation

Kwikot Industrial Water Heater Installation across Gauteng. Supply and installation of Kwikot industrial water heaters and hot water cylinders. Work covers the full Kwikot Industrial Water Heater range from the 500 L KS100 through to 3 000 L vessels, in vertical or horizontal configuration and in mild or stainless steel.

Installation covers plinth preparation, vessel positioning in vertical or horizontal configuration, flanged pipework, panel mounting and electrical connection, then commissioning against the rated recovery figure. Where the unit replaces older plant, we confirm loading and cabling before the vessel is ordered.

Vessels are lined with Carboguard 545 or glass-flake epoxy, heated by flanged Incalloy elements and controlled from 6 kW–84 kW pre-wired panels, so any repair has to consider the water side, the element side and the panel together.

Control scheduling is often the cheapest available improvement, particularly where heating windows overlap with peak tariff periods. Gauteng municipal water is moderately hard, so scale on elements and heat exchangers is the single most common cause of falling performance.

Range
500 L – 3 000 L
Turnaround
Typical single-vessel installation is one to three days on site after delivery.
Call
069 268 0988

Included

Scope of work

  • Site survey, load and storage sizing
  • Plinth and access planning
  • Flanged pipework and valve set installation
  • Control panel mounting and electrical termination
  • Safety valve, vent and drain arrangements
  • Commissioning with recorded recovery test

What we work on

Equipment specification

Flagship modelKwikot KS100 — 500 L industrial water heater
Capacity range500 L, 750 L, 1 000 L, 1 500 L, 2 000 L, 2 500 L, 3 000 L
ConfigurationVertical or horizontal, floor-standing installation
Vessel materialMild steel or stainless steel
Internal protectionCarboguard 545 or glass-flake epoxy lining
ElementsIncalloy immersion elements, flanged
RecoveryApproximately 6 hours from cold to 60 °C at rated loading
Insulation50 mm IW24 fibreglass
Cladding0.6 mm galvanised or stainless steel
Safety devicesOver-pressure and over-temperature safety valves
ControlsControl thermostat plus independent over-temperature thermostat
Working pressureUp to 400 kPa standard, 600 kPa option
Electrical loading6 kW – 84 kW pre-wired control panels, custom loading to order
Panel optionsAmmeter, voltmeter, time switch, bypass switch, stepped control, low-water cut-out
ConnectionsFlanged inlet, outlet, element and drain connections

Coverage

Areas

FAQs

Frequently asked questions

Do you work on the Kwikot KS100 500 L industrial water heater?

Yes. The KS100 500 L vessel is the most common unit we attend, and the same work applies to the 750 L, 1 000 L, 1 500 L, 2 000 L, 2 500 L and 3 000 L models in the range.

What is included in kwikot industrial water heater installation?

Site survey, load and storage sizing, Plinth and access planning, Flanged pipework and valve set installation, Control panel mounting and electrical termination — with anything additional quoted before it is carried out.

How long does it take?

Typical single-vessel installation is one to three days on site after delivery.

How long should the vessel take to recover?

Nominal recovery is about six hours from cold to 60 °C at rated electrical loading. If measured recovery is materially slower, the usual causes are scaled elements, a failed element on one phase, or a stepped control panel not bringing all stages in. Where a site runs on borehole water, hardness and iron content shorten service intervals considerably and are worth testing before setting a maintenance plan.

Where do you carry out this work?

Across Johannesburg, Ekurhuleni, West Rand, Midrand, Centurion and Pretoria. Call 069 268 0988 or email info@reyds.co.za.

Can the plant be upgraded rather than replaced?

Often, yes. Electrical loading can be increased inside panel and cabling limits, storage can be banked with a second vessel, and a heat pump can be added ahead of the cylinder to carry base load with the elements as backup.

Kwikot Industrial Water Heater Installation

Attendance across Johannesburg, Ekurhuleni, West Rand, Midrand, Centurion and Pretoria. Email info@reyds.co.za or call 069 268 0988.